QCC Quad Channel Controller

QCC Quad Channel Controller
4 channel Controller with logic control for small to medium gas detection applications
Available with Modbus® or BACnet® output for communicating with a BAS, DDC or other control panel
Applications
Large Parking Facilities, Recreation Facilities, Food Processing Plants, Cold Storage / Freezer Rooms, Chemical Storage
Rooms, and many more...
Key Features
  • Up to 4 channels of gas readings
  • QCC-M offers Modbus® RS-485 digital output signal for LAN and WAN communications
  • QCC-B offers BACnet® MS/TP output signal for WAN communications (for communicating with a BAS)
  • 4 line by 20 character LCD display with LED indicators
  • 3 dry contact relays, 5-amps @240 volts each
  • Optional two 4-20 mA outputs, includes data logging
  • Line Voltage (90-240 VAC)
  • USB port for firmware upgrades
  • Door mounted audible alarm, optional water tight version available
  • Standard water / dust tight, corrosion resistant enclosure (drip proof); IP54 rated with water tight, door
    mounted audible alarm installed

 Description
The QCC Quad Channel Controller offers 4 channels for monitoring toxic, combustible and/or refrigerant gases with 
versatile control functionality for non-hazardous, non-explosion rated, commercial and light industrial applications.
It is designed to accept inputs from up to four remote digital and/or analog transmitters using digital or 4-20 mA
analog input.
The QCC is available in two models: the QCC-M with Modbus® RS-485 output or the QCC-B with BACnet® MS/TP 
output for communicating with a Building Automation System (BAS).
Standard features include, three configurable SPDT dry contact relays with field configurable time delays and trigger 
levels, an LCD display with LED indicators for channel alarm status, relay status and fault conditions, an extensive
menu system with password protection, logic control, a USB port for firmware upgrades and a door mounted, loud
audible alarm that is ideal for noisy environments.
Optional value added features include: an analog output module with two analog outputs and data logging, a manual 
shutoff switch (meets B52 code requirements), a top mounted strobe and a water tight, door mounted audible alarm.
The QCC can be connected to several remote devices such as any of the Remote Strobe & Horns, a QCC-RDM Remote 
Display Module and the LNK-AO Analog Output Peripheral device.
 Specifications
Mechanical

Enclosure
ABS / Polycarbonate, copper coated interior to reduce RF interference IP54 rated with optional water tight, door mounted buzzer installed

Weight					1.8 kg / 4 lbs

Size					        254 x 226 x 113 mm / 10.0 x 8.9 x 4.44 inches


User Interface
Display 4x20 character LCD digital display and LED indicators for “STATUS 1, 2 and 3”
and “FAULT”

Manual Shutoff Switch			Optional: Slap button on side of enclosure (for refrigeration applications to 
meet B52 code requirements)


Input/Output

Input Modbus® RTU RS-485 4-20 mA analog

Output					Modbus® RTU RS-485 
					        Modbus® RTU RS-485 (model: QCC-M) output to BAS or DDC 
					        BACnet® MS/TP RS-485 (model: QCC-B) output to BAS or DDC 
					        One strobe / horn drive rated 0.5 amps @ 24 V max 
					        Optional: Two internal 4-20 mA analog outputs (if Option -AO is installed), 
comes with data logging

Relay					        Three internal SPDT dry contact relays rated 5 amps @ 240 VAC

Audible Alarm				Standard loud, door mounted buzzer, rated 90 dB @ 30 cm (1 ft) 
					        Optional: door mounted, water tight buzzer, rated 85 dB @ 60.96 cm (2 ft)

Top Mounted Strobe			Optional: bright, red, top mounted strobe, 10 - 30 VDC, 13 cm H x 6.1 cm dia 
/ 5.2 inches H x 2.4 inches dia


Electrical
Power Requirement Line Voltage: 90 – 240 VAC, 50 -60 Hz, 75 W

Power Distribution				Total power available for Remote & Peripheral Devices and Options 65 W 
@ 24 VDC

Wiring					Line Voltage: VAC 3-conductor shielded minimum 18 AWG stranded within 
conduit LAN Modbus® RTU (version 1.1b3) RS-485, 16 gauge, 4-conductor shielded WAN (output to BAS only): Modbus® RS-485 or BACnet® MS/TP, 4-conductor
shielded

Fuses					        Thermal, resetting


Environmental

Operating Temperature -20°C to 40°C (-4°F to 104°F)

with internal heater			-40°C to 40°C (-40°F to 104°F)

Operating Humidity			15 - 90% RH non-condensing


Certifications
Conforms to: CSA-C22.2 No. 205-12, UL508 (Edition 17):2007 EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010 FCC. This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation. QCC-B, QCC-B-X models are Listed by BTL (where X represents one or more
factory installed Options) RoHS compliant circuit boards

Technical Library   Part Numbers
Visitors: 76,833