FCS Flexible Control System (up to 128 Channels)

FCS Flexible Control System (up to 128 Channels)
128 channel high performance Controller with logic control and priority settings for mid to large gas detection 
applications
Available with Modbus® or BACnet® communication with BAS, supports 4-20 mA and Modbus® driven VFDs
Applications
Large Parking Facilities, Recreation Facilities, Food Processing Plants, Cold Storage / Freezer Rooms, Chemical Storage
Rooms, and many more...
Key Features
  • Up to 128 channels of gas readings
  • FCS-M offers Modbus® RTU RS-485 digital output signal for LAN and WAN communications
  • FCS-B offers BACnet® MS/TP RS-485 output signal for WAN communications (for communicating with a BAS)
  • Graphic, full colour, resistive rouch LCD screen with LED indicators
  • Optional internal analog inputs and/or analog outputs with flexible configuration settings
  • Enhanced logic control, zoning and priority structure capabilities
  • Supports 4-20 mA and Modbus® driven VFDs
  • 4 dry contact relays, 5-amps @240 volts each
  • Line Voltage (90-240 VAC)
  • USB port for firmware upgrades and data logging
  • Two horn/strobe output drives
  • Configurable to comply with California Title-24 Energy Efficiency Standards
  • Door mounted audible alarm, optional water tight version available
  • Standard water / dust tight, corrosion resistant enclosure (drip proof); IP54 rated with water tight, door
    mounted audible alarm installed

 Description
The FCS Flexible Control System is a sophisticated, high performance controller that offers up to 128 gas channel 
configurations for monitoring toxic, combustible and refrigerant gases with versatile control functionality for
non-hazardous, non-explosion rated, commercial and light industrial applications. The FCS is designed to accept
inputs from digital and/or analog transmitters and/or Peripheral Devices (in various combinations), using Modbus®
RTU RS-485 or 4-20 mA analog input.
The FCS is available in two models: the FCS-M with Modbus® RTU RS-485 WAN output or the FCS-B with BACnet® 
MS/TP RS-485 WAN output for communicating with a Building Automation System (BAS). Standard features include,
four configurable SPDT dry contact relays with field configurable time delays and trigger levels, a full colour LCD 
resistive touch screen with LED panel indicating configurable channel alarm status, relay status and fault conditions,
extensive menu system with password protection, enhanced logic control, priorities/zoning capabilities, a USB port
for firmware upgrades, data logging and a door-mounted, audible alarm. The FCS has flexible configuration settings
for analog outputs and supports 4-20 mA and Modbus® driven VFDs.
Optional value added features include, analog inputs and/or analog outputs, a top mounted strobe, a locking door, 
a manual shut off switch and a water tight, door-mounted audible alarm.
The FCS can be connected to several remote devices such as a remote strobe & horn, a Remote Display Module and 
several LNK Peripheral Devices. It can also be configured to comply with California Title-24 Building Energy Efficiency
Standards. (Specification details need to be given at time of order and additional settings can be implemented in
the field as required.)
 Specifications
Mechanical

Enclosure
ABS / Polycarbonate, copper coated interior to reduce RF interference IP54 rating with door mounted, water tight buzzer installed

Weight					1.8 kg / 4 lbs

Size					        254 x 226 x 113 mm / 10.0 x 8.9 x 4.44 inches


User Interface
Display 8.1 cm (3.2”) graphic, 1/4 VGA full colour resistive touch LCD screen with LED
indicators for “POWER”, “STATUS 1, 2 and 3” and “FAULT”


Input/Output
Input Modbus® RTU RS-485 input (max 128, no analog inputs) 4-20 mA analog input (optional) (max 60)

Output					Modbus® RTU RS-485 output to networked devices 
					        Modbus® RTU RS-485 (model: FCS-M) output to BAS or DDC 
					        BACnet MS/TP RS-485 (model: FCS-B) output to BAS or DDC 
					        Two drive outputs for strobe/horn - e.g. RSH-24 (0.5 amp @ 24 V max) 
					        4-20 mA analog output (optional)

Relays					Four internal SPDT dry contact relays rated 5 amps @ 240 VAC

Audible Alarm				Standard loud, door mounted buzzer, rated 90 dB @ 30 cm (1 ft) 
					        Optional: door mounted, water tight buzzer, rated 85 dB @ 60.96 cm (2 ft)

Top Mounted Strobe			Optional: bright, red, top mounted strobe, 10 - 30 VDC, 13 cm H x 6.1 cm dia 
/ 5.2 inches H x 2.4 inches dia


Electrical
Power Requirement Line Voltage: 90 – 240 VAC, 50 -60 Hz, 75 W

Current Draw				Line Voltage (110 VAC): approx. 1.0 amps 
					        Line Voltage (220 VAC): approx. 0.5 amps

Power Distribution				Total power available for Remote & Peripheral Devices and Options 65 W 
@ 24 VDC

Wiring					Line Voltage: VAC 3-conductor shielded minimum 18 AWG stranded within 
conduit LAN Modbus® RTU (version 1.1b3) RS-485, 16 gauge, 4-conductor shielded WAN (output to BAS only): Modbus® RS-485 or BACnet® MS/TP, 4-conductor
shielded

Fuses					        Thermal, resetting


Environmental
Operating Temperature -20°C to 40°C (-4°F to 104°F)

with internal heater			-40°C to 40°C (-40°F to 104°F)

Operating Humidity			15 - 90% RH non-condensing


Certifications
Conforms to: CSA-C22.2 No. 205-12, UL508 (Edition 17):2007 EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010 FCC. This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation. FCS-B, FCS-B-X models are Listed by BTL (where X represents one or more
factory installed Options) RoHS compliant circuit boards

Technical Library   Part Numbers
Visitors: 70,903