LPT-B BACnet Transmitter

LPT-B BACnet® Transmitter
For monitoring: Ammonia, Carbon monoxide, Chlorine dioxide, Chlorine, Ethylene, Ethylene oxide, Fluorine, 
Formaldehyde, Hydrogen, Hydrogen sulphide, Hydrogen chloride, Hydrogen cyanide, Hydrogen fluoride, Nitric
oxide, Nitrogen dioxide, Oxygen, Ozone, Phosphine, Silane, Sulfur dioxide, Methane, Propane, Hydrogen, TVOCs
A full featured, 3 channel, digital (BACnet®) gas detector with many gas sensor choices, intended to be used 
alone or integrated into an existing BACnet® network 
Applications
Parking Facilities, Arenas and Pools, Chiller Rooms, Manufacturing Plants, Maintenance Facilities, Food Processing
Plants, Ice Cleaning Machine Rooms and many more...
Key Features
  • 1, 2 or 3 channel operation with internal and/or remote sensor configurations
  • BACnet® MS/TP communication
  • LCD display
  • One 2A SPDT dry contact relay
  • Internal audible alarm
  • 24 VAC/VDC power
  • 4-conductor daisy chain network wiring
  • Unobtrusive calibration and menu navigation using a magnetic wand
  • Standard water / dust tight, corrosion resistant enclosure (drip proof)
  • IP54 rated with optional splash guard installed.

 Description
The LPT-B is a full featured, 3 channel, BACnet® transmitter for use in non-hazardous, non-explosion rated, 
commercial and light industrial applications. It is available with a wide range of internal and/or external sensors
and sensor types including electrochemical, catalytic and PID TVOCs.
The LPT-B may be configured to operate as a standalone fixed system or be part of a digital network. It offers a 
BACnet® MS/TP output signal for communicating with a Controller or Building Automation System, an audible
internal alarm, one SPDT dry contact relay, LCD display with user selectable functions, temperature compensation a
nd thermal resetting fuses all in a RoHS compliant package.
The LPT-B comes in a standard water / dust tight, corrosion resistant ABS / polycarbonate enclosure with a hinged, 
secured door. It is IP54 rated with the optional splash guard installed which provides protection in water spray or
wash down applications.
The LPT-B is not compatible with CETCI’s Controllers. It is intended to be used alone or integrated into an existing 
BACnet® network.
 Specifications
Target Gas

Electrochemical Sensors (internal) Ammonia (NH3), Carbon monoxide, Chlorine (Cl2), Chlorine dioxide (ClO2),
Ethylene (C2H4), Ethylene oxide (C2H4O), Fluorine (F2), Formaldehyde
(CH2O), Hydrogen (H2), Hydrogen chloride (HCl), Hydrogen cyanide (HCN),
Hydrogen fluoride (HF), Hydrogen sulphide (H2S), Nitric oxide (NO),
Nitrogen dioxide (NO2), Oxygen (O2), Ozone (O3), Phosphine (PH3),
Silane (SiH4), Sulphur dioxide (SO2), TVOCs (Isobutylene)

Catalytic Sensors (remote)			Hydrogen (H2), Methane (CH4), Propane (C3H8)

PID Sensors (remote)				TVOCs

Infrared Sensors (remote)				Propane (C3H8)


Mechanical
Enclosure
ABS / Polycarbonate, corrosion resistant Copper coated interior to reduce RF interference IP54 rated with optional splash guard installed

Weight						363 g / 0.80 lbs

Size							127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches


User Interface
Display
Graphic LCD, yellow border Magnetic switches to initiate calibration without opening the enclosure


Input/Output
Output
BACnet® MS/TP communications

Relay							One SPDT dry contact, rated at 30 volts, 2 amps max

Audible Alarm					Standard internal buzzer


Electrical
Power Requirement
16-30 VDC, 3 W, Class 2 12-27 VAC, 50-60 Hz, 3 VA, Class 2

Current Draw					55 mA (buzzer & relay energized, 2 sensors)

Wiring						4-conductor, 16 AWG stranded, shielded network wiring (daisy-chain)

Fuses							Thermal, resetting


Environmental
Operating Temperature
-20°C to 40°C (-4°F to 104°F)

Operating Humidity				15 - 90% RH non-condensing


Certifications
Conforms to
CSA-C22.2 No. 205-12 / UL508 (Edition 17):2007 EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010 FCC. This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. Listed by BTL RoHS compliant circuit boards

Technical Library   Part Numbers
Visitors: 70,677