IAM-100
Description
The IAM-100 area monitor is specifically designed to provide continuous monitoring of individual rooms in hotels, dormitories, hospitals and apartment buildings where a VRF/VRV or multi-split system is used as the air conditioning system. A refrigerant leak in such an installation could easily flood a room with a high concentration of refrigerant causing oxygen depletion at the floor level. For a less intrusive installation, the sensor can be remotely mounted from the main monitor.
If a pre-set alarm threshold is exceeded in an area, the IAM-100’s integrated audible and visual alarms are activated to alert occupants of the hazard. The two on-board relays can shut-off refrigerant supply lines, activate exhaust fans, or notify a building BMS or BAS systems. The IAM-100 can function as a standalone monitor or up to 16 units can be connected to an IAM Controller, which in turn can build a pyramid type monitoring system.
Specifications
Type | Area monitor using semiconductor sensors |
Gases | Refrigerants: HFCS, HCFCS |
Remote Sensor | Up to 32 ft (10 m) |
Measuring Range* | typically 0 to 1,000 / 10,000 ppm |
Power Supply | 110 VAC, 60 Hz or 220 VAC, 50 Hz; 11 W |
Status Indicators | Green and Red LEDs |
Audible Alarm | 85 dB buzzer (with onboard mute button) |
Relay | 2 redundant alarm relays, SPDT Rating 1 A @ 24 VDC, resistive load Alarm delay 0, 1, 5, or 10 minutes (user-selectable) |
Ambient Conditions | Temperature - 4 to +122 °F (- 20 to +50 °C) Humidity 0 to 95 %RH, non condensing Altitude 0 to 10,000 ft (0 to 3,050 m) |
Enclosure | Powder-coated Aluminum; IP30 |
Size (w x h x d) | Approx. 5.8” x 3.5” x 2.5” (150 x 90 x 65 mm) |
Weight | Approx. 22 oz (640 g) |
Approvals | CE Mark, UL / CSA/ IEC / EN 61010-1 |
* See datasheet for details